210.20 Overcurrent
Protection
What's Wrong
Here?
Code Q&A
Code Quiz
State of
Washington
Adopts Emergency Rule for Selective Coordination
|
|
About this Newsletter
|
This twice-a-month e-newsletter is brought to you from the
publisher of EC&M magazine. CodeWatch will:
Let you know what could be changing in the Code®.
Help you brush up on your ability to apply the
Code®.
Test your knowledge of the Code® with a Q&A format.
Provide information on upcoming Code® seminars and
shows.
Give you an opportunity to sound off on
Code®-related issues.
We want to make sure we're providing you with the content you need to
better manage your business or enhance your technical skills. E-mail us and let us know what
you
want to see in future issues of this e-newsletter. We will do our best
to address your request in a future issue of CodeWatch.
|
Subscriptions
|
|
To unsubscribe from this newsletter go to: Unsubscribe
To subscribe to this newsletter, go to: Subscribe
To get this newsletter in a different format (Text or HTML),
or to change your e-mail address, please visit your profile
page to change your delivery preferences.
|
Back Issues
|
|
Missed an
issue? Visit the
CodeWatch archive on EC&M's Web site.
|
Tell a friend about CodeWatch
|
|
Do you know
of someone who'd like to receive CodeWatch? Visit the subscriber site, enter
their e-mail address and spread the wealth!
|
Advertising
|
To find out
how to advertise in this newsletter, e-mail David Miller or call him at
(312) 840-8497.
The designations "National Electrical Code” and “NEC” refer to the
National Electrical Code®, which is a registered
trademark of the
National Fire Protection Association.
ADVERTISEMENT

ADVERTISEMENT

|
| | | | |
|
Top 50 NEC Rules
210.20 Overcurrent Protection
By Mike Holt
Size branch-circuit overcurrent protection devices no
less than 125% of the continuous loads plus 100% of the noncontinuous
loads they serve. See 210.19(A)(1) for branch-circuit conductor sizing
requirements. Where the assembly and the overcurrrent protection
devices
are both listed for 100% continuous load operation, you can size the
branch-circuit protection device at 100% of the continuous load.
However, note that equipment suitable for 100% continuous loading is
rarely available in ratings under 400A.
Protect branch-circuit conductors against overcurrent in accordance
with 240.4. Protect branch-circuit equipment in accordance with 240.3.
Editor's note: This information was extracted from Mike
Holt's
textbook, Understanding
the National Electrical Code
ADVERTISEMENT
Achieve Your Performance Goals
Anticipate, prevent and troubleshoot motors, electrical and equipment
maintenance with fast, accurate non-contact temperature measurements
with Fluke infrared thermometers. www.fluke.com/codewatch_temp
Code Challenge
What's Wrong Here?
By Joe Tedesco
Think you know how this installation violates the
NEC? Visit EC&M's Web
site to see the answer.
Hint: Something is missing in this installation.
Code Q&A
By Mike Holt
Q. Can Table 310.15(B)(6) be used to size
service
conductors for a duplex?
Visit EC&M's
Web site to see the answer.
Code Quiz
By Steven Owen
Q. When installing electric heat-tracing cables
and heating panels in industrial installations (where ground fault
alarm
indication is provided and the operation cannot tolerate a ground fault
condition that would normally open the circuit overcurrent device),
which of the following choices best meets the requirements outlined in
Art. 422 for protection of these components?
A) Ground fault protection for equipment is not required for the
heating cables and the heating panels where qualified persons service
the installation and continued operation is necessary for safe
operation
of the equipment or process. However, the heating wires or cables must
have a grounded conductive covering.
B) GFCI protection is required for the heating cables only, and
the cables must have a grounded conductor covering.
C) GFCI protection is required for the heating cables and
heating
panels.
D) Ground fault protection for equipment is required for the
heating cables and the heating panels, and the cables must have a
grounded conductor covering.
Visit EC&M's
Web site for the answer and explanation.
ADVERTISEMENT
Cool Electronic Cabinets
Prevent hot weather failures that can affect production. UL Listed
Cabinet Coolers from EXAIR produce 20 degree Fahrenheit air from an
ordinary supply of compressed air to cool electrical controls.
Thermostat control minimizes air usage. Maintains the NEMA 4, 4X
(stainless steel) and 12 rating of the enclosure. Web site offers
detailed information, downloadable drawings and PDF literature.
www.exair.com/15/540_07a.htm
Code News Update
State of Washington Adopts
Emergency
Rule for Selective Coordination
In a rule-making order filed on May 31, 2006, the chief
electrical inspector of the State of Washington issued an emergency
ruling that exempts existing buildings undergoing modification or
renovation from the 2005 NEC requirements for selective coordination of
emergency and legally required standby power systems. More
specifically,
the requirements for selective coordination described in 700.27 and
701.18 are not required in existing buildings or structures. However,
the portion of the emergency or legally required standby system for any
new building or structure not located within the existing building or
structure must still comply with the requirements of 700.27 and 701.18.
The reasons behind this emergency ruling were noted in the
rule-making order, which noted in part: "It was recently brought to the
department's attention that upgrading existing buildings to a
coordinated system is placing a significant economic burden on building
owners and businesses. Also, due to the increased regulatory
requirements associated with the coordinated systems, facilities such
as
hospitals and schools will have to be placed out-of-service for
extended
periods of time."
The ruling goes on to say, "The emergency rule will provide building
owners and businesses financial relief from having to upgrade the
existing emergency systems without comprising public safety."
ADVERTISEMENT
One Gets It Done.
Feel the difference with the Twister® Wire Connector. A
comfortable swept wing design provides added leverage, while the
durable
polypropylene shell expands for a smooth application. The patented
live-action, square-wire spring locks onto the wire for safe, secure
connections. Don't settle for just any wire connector. Insist on the
Twister. Visit www.idealindustries.com
for a free sample.
|
|
You are subscribed to this newsletter as #email#
For questions concerning delivery of this newsletter, please contact
our
Customer Service Department at:
Customer Service Department EC&M
A Prism Business Media publication
US Toll Free: 866-505-7173
International: 847-763-9504
Email:ecmweb@pbinews.com
Prism Business Media
9800 Metcalf Avenue
Overland Park, KS 66212
Copyright 2006, Prism Business Media. All rights reserved. This article
is protected by United States copyright and other intellectual property
laws and may not be reproduced, rewritten, distributed,
re-disseminated,
transmitted,
displayed, published or broadcast, directly or indirectly, in any
medium
without the prior written permission of Prism Business Media.
|
|