250.53
Installation of Grounding Electrode System
What's
Wrong
Here?
Code Q&A
Code Quiz
Changes in Store
for Electrical Code in Northwest Missouri Town?
Get In-Depth
Information on Code Changes & Standards
|
|
About this Newsletter
|
This twice-a-month e-newsletter is brought to you from the
publisher of EC&M magazine. CodeWatch will:
Let you know what could be changing in the Code®.
Help you brush up on your ability to apply the
Code®.
Test your knowledge of the Code® with a Q&A format.
Provide information on upcoming Code® seminars and
shows.
Give you an opportunity to sound off on
Code®-related issues.
We want to make sure we're providing you with the content you need to
better manage your business or enhance your technical skills. E-mail us and let us know what
you
want to see in future issues of this e-newsletter. We will do our best
to address your request in a future issue of CodeWatch.
|
Subscriptions
|
|
To unsubscribe from this newsletter go to: Unsubscribe
To subscribe to this newsletter, go to: Subscribe
To get this newsletter in a different format (Text or HTML),
or to change your e-mail address, please visit your profile
page to change your delivery preferences.
|
Back Issues
|
|
Missed an
issue? Visit the
CodeWatch archive on EC&M's Web site.
|
Tell a friend about CodeWatch
|
|
Do you know
of someone who'd like to receive CodeWatch? Visit the subscriber site, enter
their e-mail address and spread the wealth!
|
Advertising
|
To find out
how to advertise in this newsletter, e-mail David Miller or call him at
(312) 840-8497.
The designations "National Electrical Code” and “NEC” refer to the
National Electrical Code®, which is a registered
trademark of the
National Fire Protection Association.
ADVERTISEMENT

ADVERTISEMENT

ADVERTISEMENT

|
| | | | |
|
Top 50 NEC Rules
250.53
Installation of Grounding Electrode System
By Mike Holt
Where practicable, ground rods must be embedded below
permanent moisture level and must be free from nonconductive coatings
such as paint or enamel [250.12]. Ground rod electrodes must be
installed so that not less than 8 feet of length is in contact with the
soil. Where rock bottom is encountered, the ground rod must be driven
at
an angle not to exceed 45 degrees from vertical. If rock bottom is
encountered at an angle up to 45 degrees from vertical, the ground rod
can be buried in a minimum 30-inch-deep trench.
The upper end of the ground rod must be flush with or underground
unless the grounding electrode conductor attachment is protected
against
physical damage as specified in 250.10. See 250.52(A)(5) and 250.53(A)
for additional details. When the grounding electrode attachment fitting
is located underground, it must be listed for direct soil burial
[250.68(a) Ex. 1, and 250.70].
Where more than one grounding electrode system exists at a building
or structure, they must be separated by at least 6 feet.
Where within 18 inches of earth, the conductor used to bond
grounding
electrodes together to form the grounding electrode system must be
copper [250.64(A)], securely fastened to the surface on which it's
carried, and be protected if exposed to physical damage [250.64(B)].
The
bonding jumper to each electrode must be sized in accordance with
250.66.
In addition, the grounding electrode bonding jumpers must terminate
to the grounding electrode by exothermic welding, listed lugs, listed
pressure connectors, listed clamps, or other listed means [250.8]. When
the termination is encased in concrete or buried, the termination
fittings must be listed and identified for this purpose [250.70].
The bonding connection to the interior metal water piping system, as
required by 250.104(A), must not be dependent on water meters,
filtering
devices, or similar equipment likely to be disconnected for repairs or
replacement. When necessary, a bonding jumper must be installed around
insulated joints and equipment likely to be disconnected for repairs or
replacement to assist in clearing and removing dangerous voltage on
metal parts because of a ground fault. See 250.68(B) and 250.104 for
additional details.
The underground metal water pipe grounding electrode, if present
[250.52(A)(1)], must be supplemented by one of the following
electrodes:
- Metal frame of the building or structure [250.52(A)(2)]
- Concrete-encased steel [250.52(A)(3)]
- Ground ring [250.52(A)(4)
Where none of the above electrodes are available, one of the following
electrodes must be used:
- Ground rod in accordance with 250.56 [250.52(A)(5)
- Grounding plate [250.52(A)(6)]
- Metal underground systems [250.52(A)(7)]
The underground water pipe supplemental electrode must terminate to one
of the following:
- Grounding electrode conductor
- Grounded neutral service conductor
- Metal service raceway
- Service equipment enclosure
Where the supplemental electrode is a ground rod, that portion that is
the sole connection to a ground rod isn't required to be larger than 6
AWG copper. The bonding jumper for the underground metal water pipe
supplemental electrode is sized in accordance with 250.66, including
Table 250.66, where applicable.
If working with a ground ring, it must encircle the building or
structure, consist of at least 20 feet of bare copper conductor not
smaller than 2 AWG, and be buried at a depth not less than 30 inches.
See 250.52(A)(4) for additional details.
If working with a plate electrode, it must not have less than 2
square feet of surface exposed to exterior soils and installed so that
it's at least 30 inches below the surface of the earth [250.52(A)(6)].
Editor's note: This information was extracted from Mike
Holt's
textbook, Understanding
the National Electrical Code.
ADVERTISEMENT
Fluke 1735 Three-Phase Power Logger
Power quality logging, electrical load studies and energy consumption
testing. The Fluke 1735 Power Logger is the ideal electrician or
technician's power meter for conducting energy studies and basic power
quality logging. Set the Power Logger up in seconds with the included
flexible current probes and color display. The power quality meter
measures most electrical power parameters, harmonics, and captures
voltage events. www.fluke.com/1735Codewatch
Code Challenge
What's Wrong Here?
By Joe Tedesco
Think you know how this installation violates the
NEC? Visit EC&M's Web
site to see the answer.
Hint: Seems a little tight here, doesn't it?
Code Q&A
By Mike Holt
Q. Can Table 310.15(B)(6) be used to size
service
conductors to a duplex, where there is no firewall separating the
units?
Visit EC&M's
Web site to see the answer.
Code Quiz
By Steven Owen
Q. Where more than one equipment grounding or
bonding conductor of a branch circuit enters a box, all such conductors
shall be in good electrical contact with each other, and the
arrangement
shall be such that the disconnection or removal of a receptacle,
luminaire (fixture), or other device fed from the box will not
interfere
with or interrupt the grounding continuity. Where is this section found
in the 2005 NEC?
A) 110.12(C)
B) 250.148
C) 300.13(B)
D) 551.55(E)
Visit EC&M's
Web site for the answer and explanation.
ADVERTISEMENT
One-touch automated design and one-touch automated protective device
coordination options available in EasyPower 8.0 will be introduced in
the Hands-On training in Houston, TX, February 5-9, 2007!
Streamline
the implementation of your Arc Flash and Electrical Safety Program.
What
used to take hours, now takes mere seconds! EasyPower delivers
Windows®-based tools for designing, analyzing, and
monitoring electrical power systems.
www.easypower.com/support_training.php
Code News Update
Changes in Store for Electrical
Code
in Northwest Missouri Town?
Based on a report in the Dec. 6th edition of the St.
Joseph News-Press, the city's Electrical Standards and Appeals
Board
and
city building development staff have been working for years to come up
with changes to its electrical code.
According to the article, "Master electricians must pass a third-party
test to earn their licenses. One of the changes would require master
electrician applicants to appear before the board for a second, brief
test to evaluate their experience."
But the article goes on to point out that the board only meets
quarterly, which potentially sets up a three-month waiting period for
qualified electricians to get a license. Opponents of this change say
it
will create a barrier for out-of-town competition. Supporters of this
change say there are plenty of local electric companies to meet the
city's needs.
ADVERTISEMENT
Cool Electronic Cabinets
Stop electronic control downtime due to heat, dirt and moisture. UL
Listed Cabinet Coolers from EXAIR produce 20 degree Fahrenheit air from
an ordinary supply of compressed air to cool electrical controls.
Thermostat control minimizes air usage. Maintains the NEMA 4, 4X
(stainless steel) and 12 rating of the enclosure. Web site offers
detailed information, downloadable drawings and PDF literature.
www.exair.com/15/540_12a.htm
Shows and Events
Get In-Depth Information on Code
Changes & Standards
Are you a residential, industrial, commercial, or
institutional electrical contractor? Do you specify equipment or review
construction plans? Do you maintain electrical systems in a facility?
If
you answered "yes" to any of these questions then you have to make
plans
to attend the Electric West conference program next year in Long Beach,
Calif. Attend one of 12 fact-filled seminars, three of which offer
CEUs.
Or make plans to attend one of two update sessions on the 2005 NEC, led
by top trainer Mike Holt. These Code sessions will also offer a sneak
preview of proposed changes to the 2008 NEC. Check
out this event's 40+ seminars and make plans to meet 200+ leading
suppliers. Or register
now.
Enter The "You Be The Electrical Inspector" Contest at The
e-Tradeshow
Here's your chance to win a $100 American Express gift certificate and
show off your knowledge of the National Electrical Code by acting as an
electrical inspector and citing every Code violation appearing in five
actual electrical installations.
Submit your respective list of violations and, if you're selected as
a winner, achieve fame for your keen observation capabilities and NEC
familiarity by having your picture posted in the EC&M booth on
the e-Tradeshow exhibit floor. And, of course, don't forget about the
$100 gift certificate!
Click here for
information
on accessing the EC&M e-Tradeshow, a virtual online exhibition
and live conference center. Also available on the site is an archive of
various past presentations, such as Claim Litigation and
Harmonics: Causes, Symptoms, and Remedial Solutions.
ADVERTISEMENT
One Gets It Done.
Feel the difference with the Twister® Wire Connector. A
comfortable
swept wing design provides added leverage, while the durable
polypropylene shell expands for a smooth application. The patented
live-action, square-wire spring locks onto the wire for safe, secure
connections. Don't settle for just any wire connector. Insist on the
Twister. Visit www.idealindustries.com
for a free sample.
|
|
You are subscribed to this newsletter as #email#
For questions concerning delivery of this newsletter, please contact
our
Customer Service Department at:
Customer Service Department EC&M
A Prism Business Media publication
US Toll Free: 866-505-7173
International: 847-763-9504
Email:ecmweb@pbinews.com
Prism Business Media
9800 Metcalf Avenue
Overland Park, KS 66212
Copyright 2006, Prism Business Media. All rights reserved. This article
is protected by United States copyright and other intellectual property
laws and may not be reproduced, rewritten, distributed,
re-disseminated,
transmitted,
displayed, published or broadcast, directly or indirectly, in any
medium
without the prior written permission of Prism Business Media.
|
|