| CONTENTS
|
250.64
Grounding Electrode Conductor Installation
What's Wrong
Here?
Code Q&A
Code Quiz
Code Committee
Call-Up
It's Time to Hit
the Beach
|
|
About this Newsletter
|
This twice-a-month e-newsletter is brought to you from the
publisher of EC&M magazine. CodeWatch will:
Let you know what could be changing in the Code®.
Help you brush up on your ability to apply the Code®.
Test your knowledge of the Code® with a Q&A format.
Provide information on upcoming Code® seminars and
shows.
Give you an opportunity to sound off on Code®-related
issues.
We want to make sure we're providing you with the content you need to
better manage your business or enhance your technical skills. E-mail us and let us know what
you
want to see in future issues of this e-newsletter. We will do our best
to address your request in a future issue of CodeWatch.
|
Subscriptions
|
|
To unsubscribe from this newsletter go to: Unsubscribe
To subscribe to this newsletter, go to: Subscribe
To get this newsletter in a different format (Text or HTML),
or to change your e-mail address, please visit your profile
page to change your delivery preferences.
|
Back Issues
|
|
Missed an
issue? Visit the
CodeWatch archive on EC&M's Web site.
|
Tell a friend about CodeWatch
|
|
Do you know
of someone who'd like to receive CodeWatch? Visit the subscriber site, enter
their e-mail address and spread the wealth!
|
Advertising
|
To find out
how to advertise in this newsletter, e-mail David Miller or call him at
(312) 840-8497.
The designations "National Electrical Code” and “NEC” refer to the
National Electrical Code®, which is a registered
trademark of the
National Fire Protection Association.
ADVERTISEMENT

ADVERTISEMENT

ADVERTISEMENT

|
| | | | |
|
Top 50 NEC Rules
250.64
Grounding Electrode Conductor Installation
By Mike Holt
Aluminum grounding conductors cannot be in contact with
earth, masonry, or subjected to corrosive conditions. When used
outdoors, the termination to the electrode must not be within 18 inches
of earth.
Where exposed, grounding electrode conductors sized 8 AWG and
smaller
must be installed in rigid metal conduit, intermediate metal conduit,
rigid nonmetallic conduit, or electrical metallic tubing. Ferrous metal
raceways containing the grounding electrode conductors must be made
electrically continuous by bonding each end of the ferrous metal
raceway
to the grounding electrode conductor [250.64(E)]. Grounding electrode
conductors 6 AWG copper and larger can be run exposed along the surface
if securely fastened to the construction and not subject to physical
damage.
The grounding electrode conductor, which runs to any convenient
grounding electrode [250.64(F)], must not be spliced, except as
permitted in (1) through (3):
- Splicing is permitted by irreversible compression-type connectors
listed for grounding or by exothermic welding.
- Sections of busbars can be connected together to form a grounding
electrode conductor.
- Bonding and grounding electrode conductors are permitted to
terminate to a busbar that is sized not smaller than 1/4 x 2 inches,
and the busbar must be securely fastened in place at an accessible
location. Connections must be made by a listed connector or by the
exothermic welding process.
Click here
to read the rest of this article.
Editor's note: This information was extracted from Mike Holt's
textbook, Understanding
the National Electrical Code.
ADVERTISEMENT
Fluke 1735 Three-Phase Power Logger
Power quality logging, electrical load studies and energy consumption
testing. The Fluke 1735 Power Logger is the ideal electrician or
technician's power meter for conducting energy studies and basic power
quality logging. Set the Power Logger up in seconds with the included
flexible current probes and color display. The power quality meter
measures most electrical power parameters, harmonics, and captures
voltage events. www.fluke.com/1735Codewatch
Code Challenge
What's Wrong Here?
By Joe Tedesco
Think you know how this installation violates the
NEC? Visit EC&M's Web
site to see the answer.
Hint: Is this tube blowing or sucking air?
Code Q&A
By Mike Holt
Q. How do I size the circuit conductors and
protection device for a 25-hp, 208V, 3-phase fire pump design letter B
motor if not supplied by an on-site generator?
Visit EC&M's
Web site to see the answer.
Code Quiz
By Steven Owen
Q. What is the required working space for an
installation of an electric sign transformer, ballast, or power supply
located above a suspended ceiling? The location is such that it is
considered to be accessible. The equipment is securely fastened in
place, independent of the suspended ceiling grid.
A) Three feet in the direction of access, 2 feet -- 6 inches
wide, and 6 feet -- 6 inches high.
B) Three feet in the direction of access, 3 feet wide, and 3
feet
high.
C) 3 feet -- 6 inches in the direction of access, 3 feet wide,
and 6 feet -- 6 inches high.
D) Sufficient access and working space is all that is required
for this installation.
Visit EC&M's
Web site for the answer and explanation.
ADVERTISEMENT
Breakthrough Automation Available in
EasyPower® 8.0
See EasyPower's full lineup of Windows®-based electrical
power systems software tools!
New Features revolutionize the way you work:
SmartDesign automatically sizes feeders, breakers, fuses,
switchgear, busway, MCCs, panels -- and more -- all per NEC
requirements.
SmartPDC completely automates the tedious coordination of
protective devices. Verify compliance, generate impressive reports, and
ensure system reliability with one-touch automation. www.EasyPower.com
Code News Update
Code Committee Call-Up
Got some extra time on your hands? Looking to put some
of your vast knowledge of the electrical field to use? NFPA is looking
for new members for several of its committees, including the
following:
- Committee on Electrical Equipment in Chemical Atmospheres. This
committee is responsible for NFPA 496, Standard for Purged and
Pressurized Enclosures for Electrical Equipment; NFPA 497,
Recommended Practice for the Classification of Flammable Liquids,
Gases, or Vapors and of Hazardous (Classified) Locations for Electrical
Installations in Chemical Process Areas; and NFPA 499,
Recommended Practice for the Classification of Combustible Dusts and
of Hazardous (Classified) Locations for Electrical Installations in
Chemical Process Areas
- Committee on Electrical Equipment of Industrial Machinery (seeking
members in all categories except end users or manufacturers). This
committee is responsible for NFPA 79, Electrical Standard for
Industrial Machinery.
- Committee on Electrical Systems Maintenance (special experts
excluded). This committee is responsible for NFPA 73, Electrical
Inspection Code for Existing Dwellings.
- Committee on Health Care Facilities -- Electrical Systems. This
committee is responsible for chapters within NFPA 99, Standard for
Health Care Facilities
Anyone interested in serving can download the application form at NFPA's Web
site.
ADVERTISEMENT
Cool Electronic
Cabinets
EXAIR's low cost Cabinet Coolers stop electronic control downtime due
to
heat, dirt and moisture. UL Listed Cabinet Coolers produce 20 degree
Fahrenheit air from an ordinary supply of compressed air to cool
electrical controls. Thermostat control minimizes air usage. Maintains
the NEMA 4, 4X (stainless steel) and 12 rating of the enclosure. Web
site offers detailed information, downloadable drawings and PDF
literature.
Shows and Events
It's Time to Hit the Beach
If it's your job to make sure all systems are "go," you
need to go to Electric West. This show and conference offers the right
information and product mix to meet all of your information needs. Do
you maintain and operate electrical systems in a facility? If so, you
have to make plans to attend the Electric West conference program in
Long Beach, Calif. Check
out this event's 40+ seminars in the areas of power quality,
safety,
Code changes, and industrial applications, and make plans to meet 200+
leading suppliers. Or register
now.
|
|
You are subscribed to this newsletter as #email#
For questions concerning delivery of this newsletter, please contact
our
Customer Service Department at:
Customer Service Department EC&M
A Prism Business Media publication
US Toll Free: 866-505-7173
International: 847-763-9504
Email:ecmweb@pbinews.com
Prism Business Media
9800 Metcalf Avenue
Overland Park, KS 66212
Copyright 2006, Prism Business Media. All rights reserved. This article
is protected by United States copyright and other intellectual property
laws and may not be reproduced, rewritten, distributed,
re-disseminated,
transmitted,
displayed, published or broadcast, directly or indirectly, in any
medium
without the prior written permission of Prism Business Media.
|
|