| CONTENTS
|
440.22
Short-Circuit and Ground-Fault Protection Devices for A/C and
Refrigeration Equipment
What's Wrong
Here?
Code Q&A
Code Quiz
Deadline Fast
Approaching
Visit The EC&M
e-Tradeshow
|
|
About this Newsletter
|
This twice-a-month e-newsletter is brought to you from the
publisher of EC&M magazine. CodeWatch will:
Let you know what could be changing in the Code®.
Help you brush up on your ability to apply the
Code®.
Test your knowledge of the Code® with a Q&A format.
Provide information on upcoming Code® seminars and
shows.
Give you an opportunity to sound off on
Code®-related
issues.
We want to make sure we're providing you with the content you need to
better manage your business or enhance your technical skills. E-mail us and let us know
what you want to see in future issues of this e-newsletter. We will do
our best to address your request in a future issue of CodeWatch.
|
Subscriptions
|
|
To unsubscribe from this newsletter go to: Unsubscribe
To subscribe to this newsletter, go to: Subscribe
To get this newsletter in a different format (Text or HTML),
or to change your e-mail address, please visit your profile
page to change your delivery preferences.
|
Back Issues
|
|
Missed an
issue? Visit the
CodeWatch archive on EC&M's Web site.
|
Tell a friend about CodeWatch
|
|
Do you know
of someone who'd like to receive CodeWatch? Visit the subscriber site, enter
their e-mail address and spread the wealth!
|
Advertising
|
To find out
how to advertise in this newsletter, e-mail David Miller or call him at
(312) 840-8487.
The designations "National Electrical Code? and ?NEC? refer to the
National Electrical Code®, which is a registered
trademark of the
National Fire Protection Association.
ADVERTISEMENT

ADVERTISEMENT

|
| | | | |
|
Top 50 NEC Rules
440.22
Short-Circuit and Ground-Fault Protection Devices for A/C and
Refrigeration Equipment
By Mike Holt
Short-circuit and ground-fault protection for
air-conditioning and refrigeration equipment must be sized no larger
than identified on the equipment's nameplate. If the equipment doesn't
have a nameplate specifying the size and type of protection device,
then
the protection device must be sized in accordance with (A) or (B).
(A) One Motor Compressor. The short-circuit and ground-fault
protection device must not be greater than 175% of the motor-compressor
current rating. If the protection device sized at 175% isn't capable of
carrying the starting current of the motor-compressor, the next size
larger protection device can be used, but in no case can it exceed 225%
of the motor-compressor current rating.
(B) Rating for Equipment. Where the equipment incorporates
more than one hermetic refrigerant motor-compressor, or a hermetic
refrigerant motor-compressor and other motors or other loads, the
equipment short-circuit and ground-fault protection must be sized as
follows:
(1) Motor-Compressor Largest Load. The rating of the
branch-circuit short-circuit and ground-fault protective device must
not
be greater than the largest motor-compressor short-circuit ground-fault
protection device, plus the sum of the rated load currents of the other
compressors.
The branch-circuit conductors are sized at 125% of the larger
motor-compressor current, plus the sum of the rated load currents of
the
other compressors [440.33].
Editor's note: This information was extracted from Mike
Holt's
textbook, Understanding
the National Electrical Code
ADVERTISEMENT
The Fluke 1735 Power Logger is the ideal electrician or technician's
power meter for conducting energy studies and basic power quality
logging. Set the Power Logger up in seconds with the included flexible
current probes and color display. The power quality meter measures most
electrical power parameters, harmonics, and captures voltage events. www.fluke.com/codewatch
Code Challenge
What's Wrong Here?
By Joe Tedesco
Think you know how this installation violates the
NEC? Visit EC&M's
Web site to see the answer.
Hint: Damaged equipment in Las Vegas.
Code Q&A
By Mike Holt
Q. A 400A service is made up of two 200A main
breaker panelboards that are nippled together. Can the service
conductors pass through one of the cabinets to supply the other
panelboard?
Visit EC&M's Web
site to see the answer.
Code Quiz
By Steven Owen
Q. What is the allowable ampacity of any one of
the current-carrying 12 AWG THHN insulated conductors installed in a
cellular concrete floor raceway with 29 other current-carrying 12 AWG
THHN conductors and five equipment grounding conductors? Disregard the
terminals in your calculations.
- 30A
- 20A
- 13.5A
- 11.25A
Visit EC&M's
Web site for the answer and explanation.
ADVERTISEMENT
A full week devoted to your Arc Flash Safety Needs! Learn how to do
Arc Flash analysis, gain a full day of NFPA-70E Safety
specifics, and Witness an actual Arc Blast during our Arc
Flash Safety Emphasis Week: March 31 April 4, 2008 in Boston,
MA.
Streamline your Electrical Safety Program; what used to take hours, now
takes mere seconds with EasyPower! Learn more: www.easypower.com/support_training.php
Code News Update
Deadline Fast Approaching
The Notice of Intent to Make a Motion closing date for
the next revision of NFPA 70E: Standard for Electrical Safety in the
Workplace is April 4, 2008. This standard addresses "electrical safety
requirements for employee workplaces that are necessary for the
practical safeguarding of employees in their pursuit of gainful
employment." The posting of certified Notice of Intent to Make an NEC
Motions (NITMAMs) is scheduled to take place on May 4, 2008.
ADVERTISEMENT
Cool Electronic Cabinets
Stop electronic control downtime due to heat, dirt and moisture. UL
Listed Cabinet Coolers from EXAIR produce 20 degree Fahrenheit air from
an ordinary supply of compressed air to cool electrical controls.
Thermostat control minimizes air usage. Maintains the NEMA 4, 4X
(stainless steel) and 12 rating of the enclosure. Web site offers
detailed information, downloadable drawings and PDF literature.
www.exair.com/15/540_03a.htm
Shows and Events
Visit The EC&M e-Tradeshow
Look for these FREE live conferences, scheduled for 2008:
- Using the Electrical Designer's Reference Software Program
- The NEC in Construction Litigation
- Understanding Electrical Safety and PPE Selection
- Implementing an Arc Flash Safety Compliance Program
- Preparing an Arc Flash Hazard Study
- Proper Working Drawings: An Engineer's Perspective
Visit the many exhibitors in this virtual tradeshow and take a look at
the On-Demand Theater, where you can view past online conferences
24/7/365.
Go to e-tradeshow for
information on accessing the EC&M e-Tradeshow and visiting the
On-Demand Library.
ADVERTISEMENT
Eliminate Red
Tags
It takes more than the UL Mark on a product to satisfy code
requirements. Before your next installation, use UL's Code Compliance
Database to identify the correlation between model codes and UL
Certified products, as well as find manufacturers of certified
products.
Click here today to
find up-to-date UL Listed products at the UL Code Correlation Database.
|
|
You are subscribed to this newsletter as #email#
For questions concerning delivery of this newsletter, please contact
our
Customer Service Department at:
Customer Service Department EC&M
A Penton Media publication
US Toll Free: 866-505-7173
International: 847-763-9504
Email:ecmweb@pbinews.com
Penton Media | 249 W. 17th Street | New York, NY 10011
Copyright 2007, Penton Media, Inc. All rights reserved. This article is
protected by United States copyright and other intellectual property
laws and may not be reproduced, rewritten, distributed,
re-disseminated,
transmitted,
displayed, published or broadcast, directly or indirectly, in any
medium
without the prior written permission of Penton Media, Inc.
|
|